Eaton MTL4546/C/Y-MTL5546/Y MTL Intrinsically Safety Intrinsically Safe Isolators MTL 5500 range 1ch 4-20mA smart isolating driver+LFD
Isolating Driver for 4-20mA HART® valve positioners with line fault detection
Similar Types : MTL5018AC, MTL5501-SR, MTL5510, MTL5510B, MTL5511, MTL5513, MTL5514, MTL5514D, MTL5516C, MTL5517, MTL5521, MTL5522, MTL5523, MTL5523V-VL, MTL5524, MTL5525, MTL5526, MTL5541, MTL5541A, MTL5541AS, MTL5541S, MTL5544, MTL5544A, MTL5544AS, MTL5544D, MTL5544S, MTL5546, MTL5546Y, MTL5549, MTL5549Y, MTL5573, MTL5575, MTL5576-RTD, MTL5576-THC, MTL5581, MTL5582, MTL5582B, MTL5531, MTL5532, MTL5561, MPA5500, MTL5051, MTL5053, MTL5314, MTL5599, PSG60E24RM (replaces MTL5991)
The MTLx546 accepts a 4/20mA floating signal from a safe-area controller to drive a current/pressure converter (or any other load up to 800Ω) in a hazardous area. For HART valve positioners, the module also permits bi-directional transmission of digital communication signals. Process controllers with a readback facility can detect open or short circuits in the field wiring: if these occur, the current taken into the terminals drops to a preset level. The MTL4546C and the MTLx546Y are very similar to the MTLx546 except that they provide open circuit detection only
(i. e. no short-circuit detection).
Number of channels
One
Location of I/P converter
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A, hazardous location
Working range
4 to 20mA
Digital signal bandwidth
500Hz to 10kHz
Maximum load resistance
800Ω (16V at 20mA)
Minimum load resistance
90Ω (short-circuit detection at < 50Ω)
Output resistance
> 1MΩ
Under/over range capability
Under range = 1mA
Over range = 24mA (load ≤ 520Ω)
Input and output circuit ripple
< 40µA peak-to-peak
Transfer accuracy at 20°C
Better than 20µA
Temperature drift
< 1.0µA/°C
Input characteristics
Field wiring state | MTLx546 | MTL4546C | MTLx546Y |
Normal | < 6.0V | < 6.0V | < 6.0V |
Open-circuit | < 0.9mA | < 0.9mA | < 0.5mA |
Short-circuit | < 0.9mA | N.A. | N.A. |
Response time
Settles within 200µA of final value within 100ms
Communications supported
HART
LED indicator
Green: power indication
Maximum current consumption (with 20mA signals into 250Ω load)
35mA at 24V dc
Power dissipation within unit (with 20mA signals into 250Ω load)
0.8W at 24V
Safety description
Uo=28V Io=93mA Po=651mW Um = 253V rms or dc