WUHAN XIEYUAN AUTOMATION EQUIPMENT CO., LIMITED
|
Qty (Piece/Pieces) | Unit Price (20.0~2000.0 USD) |
1 | 20 |
1 + | 2000 |
Trade Term: | FOB,EXW |
Payment Terms: | T/T,WU,Paypal |
Place of Origin: | Hubei, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Eaton MTL4516/C-MTL5516C Switch/ Proximity Detector Interface 2-channel with line fault detection MTL Intrinsic Safety Intrinsically Safe Isolators MTL5500 range
2ch DI with changeover relay output
The MTLx516/C enable two safe-area loads to be controlled by a switch or proximity detector located in a hazardous-area. When selected, open or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the top of the module.
Phase reversal for each channel is selected by a switch on the side of the module and output is provided by changeover relay contacts.
SPECIFICATION
Number of channels Two
Location of switches Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous location
Location of proximity detector Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A hazardous location
Hazardous-area inputs Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor 7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. Line faults are
indicated by an LED for each channel. The channel output relay is
de-energised if an input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Safe-area output
Two single-pole relays with changeover contacts
Note: reactive loads must be adequately suppressed
Relay characteristics
MTL4516/C | MTL5516C | |
Response time: | 10ms maximum | 10ms maximum |
Contact rating (Safe Area): | 10W, 0.5A, 35V dc | 250V ac, 2A, cosØ >0.7, 40V dc, 2A, resistive load |
Contact rating (Zone 2): | 10W, 0.5A, 35V dc | 35V, 2A, 100VA. |
Maximum current consumption 35mA at 24V
Power dissipation within unit 0.84W at 24V
LED indicators
Green: power indication
Yellow: two: channel status, on when output energised
Red: two: LFD indication, on when line fault detected
Safety description (each channel)
Uo=10.5V Io=14mA Po=37mW Um = 253V rms or dc
Similar model codes for your reference :
MTL5018AC, MTL5501-SR, MTL5510, MTL5510B, MTL5511, MTL5513, MTL5514, MTL5514D, MTL5516C, MTL5517, MTL5521, MTL5522, MTL5523, MTL5523V-VL, MTL5524, MTL5525, MTL5526, MTL5541, MTL5541A, MTL5541AS, MTL5541S, MTL5544, MTL5544A, MTL5544AS, MTL5544D, MTL5544S, MTL5546, MTL5546Y, MTL5549, MTL5549Y, MTL5573, MTL5575, MTL5576-RTD, MTL5576-THC, MTL5581, MTL5582, MTL5582B, MTL5531, MTL5532, MTL5561, MPA5500, MTL5051, MTL5053, MTL5314, MTL5599, PSG60E24RM (replaces MTL5991)